Table 6-2
Configuration Table and Address Space
Slot
1
6ES7 138-4CA00-0AA0 PM-E 24 VDC
2
6ES7 131-4BB00-0AB0 2DI 24 VDC
3
6ES7 131-4BB00-0AB0*2DI 24 VDC
4
6ES7 134-4FB00-0AB0 2AI U
5
6ES7 135-4GB00-0AB0 2AO I
6
6ES7 131-4BD00-0AA0*4DI 24 VDC
7
6ES7 132-4BD00-0AA0 4DO 24 VDC
8
6ES7 132-4BB00-0AB0*2DO 24 VDC
9
6ES7 132-4HB00-0AB0*2DO Rel.
10
6ES7 134-4FB00-0AB0 2AI U
11
6ES7 135-4GB00-0AB0 2AO I
12
6ES7 138-4CA00-0AA0 PM-E 24 VDC
13
6ES7 132-4BB30-0AB0 2DO 24 VDC
14
6ES7 132-4BB30-0AB0* 2DO 24 VDC
15
6ES7 138-4CA00-0AA0 PM-E AC230
16
6ES7 132-4FB00-0AB0* 2DO 230 V
17
6ES7 132-4FB00-0AB0* 2DO 230 V
18
3RK1903-0BA00 PM-D
19
3RK1301-xxB00-0AA0 DS
20
3RK1301-xxB00-0AA0 *DS
21
3RK1301-xxB00-0AA0 DS
No Grouping
If you do not want to group the configuration of the ET 200S distributed I/O system
digital input/output modules and motor starters in a single byte, use only those
module designations without "*" in the hardware catalog of your configuration
software.
Each electronic module/motor starter will then occupy one byte in the input or
output area of the process image.
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Module
Commissioning and Diagnostics
Grouping
I/O Address
Inputs
–––
–––
Yes
0.0 to 0.1
0.2 to 0.3
No
1 to 4
No
Yes
0.4 to 0.7
Yes
No
5 to 8
No
–––
–––
Yes
Yes
–––
–––
Yes
Yes
–––
–––
Yes
9.0 to 9.3
9.4 to 9.7
Yes
10.0 to 10.3
Outputs
–––
0 to 3
4.0 to 4.3
4.4 to 4.5
4.6 to 4.7
5 to 8
–––
9.0 to 9.1
9.2 to 9.3
–––
9.4 to 9.5
9.6 to 9.7
–––
10.0 to 10.3
10.4 to 10.7
11.0 to 11.3
6-9