5.4
Wiring the ET 200S
Section
5.4.1
5.4.2
5.4.3
5.4.4
5.4.5
5.4.6
Wiring Rules for the ET 200S
Wiring Rules for ...
Connectable wire cross-sections for rigid
lines
Connectable wire
Without wire end
cross-sections for
ferrule
flexible lines
With wire end ferrule
Number of wires per connection
Maximum external diameter of the wire's
insulation
Stripping length of the wires
Wire end ferrules
Without insulating
to DIN 46228
collar
With insulating collar
0.25 to 1.5 mm
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Wiring a Terminal Module with Screw-Type Terminals
Wiring a Terminal Module with Spring Terminals
Wiring Terminal Modules with Fast Connect
Wiring Terminal Modules
Wiring the IM151-1 BASIC, IM151-1 STANDARD and
IM151-1 HIGH FEATURE Interface Modules
Wiring the IM151-1 FO STANDARD Interface Module
Interface Module
(Supply Voltage)
No
0.25 mm to
2
2.5 mm
0.25 mm to
2
1.5 mm
1 or a combination of 2 wires up to
2
1.5 mm
(sum) in a common wire end
ferrule
∅ 3.8 mm
11 mm
Design A, 8 to
12 mm long
Design E, up to 12 mm long
2
Description
Terminal Modules
(Spring and
Screw-Type
Terminals)
0.14 mm to
2
2.5 mm
0.14 mm to
2
2.5 mm
0.14 mm to
2
1.5 mm
∅ 3.1 mm
2
for 1.5 mm
∅ 3.8 mm for
2
2.5 mm
Design A, up to
12 mm long
Wiring and Fitting
Page
5-8
5-8
5-10
5-14
5-19
5-20
Terminal Module
(Fast Connect)
2
0.5 to 1.5 mm
2
0.5 to 1.5 mm
---
1
∅ 3.1 mm for
2
1.5 mm
---
---
---
5-7