6.2.5.9
Trip points setting
Set the flow rate and switching service and standby duration.
Info
Only visible in system 14.
Info
Visible only on master valve, identified by
Info
Depending on the number of tank used in the system, there might up to 7 trip point to
set up (for 8 tanks systems). Each additional trip point might be set for a flow rate equal
to the previous one plus 1 l/min.
a) Set the trip point flow rate with
ð Can be adjusted from 1 to 7569 l/min;
b) Press
next parameter;
c) Set the trip point service duration with
ð Can be adjusted from 1 to 90 seconds;
d) Press
next parameter;
e) Set the trip point service standby with
ð Can be adjusted from 60 to 300 seconds;
f) Press
next parameter.
6.2.5.10 Valve type
Select which valve is being used with the NXT2.
Options:
• 2510
• 2750;
• 2850;
• 2900/2910;
• 3150;
• 3900;
• 2815.
Ref. MKT-IM-010 / C - 18.10.2019
Installer manual Fleck 3150 NXT/NXT2 - Programming
to validate the selection and advance to the
to validate the selection and advance to the
to validate the selection and advance to the
on the controller screen.
,
and ;
,
and ;
,
and ;
Example: trip point #1.
99 / 182