Electrical
Controller operating voltage
Input supply frequency
Transformer voltage
Motor input voltage until March 2019
Motor input voltage April 2019 onwards
Controller power consumption
Controller protection rating
Valve protection rating
Power supply
Transient overvoltages
Pollution Degree
Temporary overvoltages must be limited in duration and in frequency.
Model without transformer
CAUTION
A switch or circuit-breaker must be included in the installation, it must be suitably
located and easily reached, it must be marked as the disconnecting device for the
equipment.
CAUTION
The power must be achieved by a transformer in which the primary windings are
separated from the secondary windings by REINFORCED INSULATION, DOUBLE
INSULATION, or a screen connected to the PROTECTIVE CONDUCTOR TERMINAL.
CAUTION
It is required the installation of a fuse as overcurrent protection, it has to be positioned
between the system and the secondary of the transformer in the installation with the
following characteristics: V ≥ 30 VDC or VAC, Imax = 5.0A (ES. 5x20 5.0A)
Environmental conditions
• Indoor use only;
• temperature from 5°C to 40°C;
• maximum relative humidity 80% for temperatures up to 31°C decreasing linearly
to 50% relative humidity at 40°C;
• mains supply voltage fluctuations up to ±10% of the nominal voltage.
Ref. MKT-IM-010 / C - 18.10.2019
Installer manual Fleck 3150 NXT/NXT2 - Description
24 VAC for NXT / 24 VDC for NXT2
50 or 60 Hz (controller configuration
dependent)
24 VAC for NXT / 24 VDC for NXT2
24 VAC
24 VDC with AC-DC inverter
60 W
IP 22
IP 44
230 VAC, 50/60 Hz,60 VA, Class II
within the limits of category II
3
15 / 182