Pentair FLECK 3150 NXT Installer Manual page 111

Hide thumbs Also See for FLECK 3150 NXT:
Table of Contents

Advertisement

• off.
a) Set continuous flow on with
b) Default setting: off;
c) Press
next parameter;
d) Adjust flow rate with
e) Can be adjusted from: 0.1 to 227.1 l/min;
f) Press
next parameter;
g) Adjust duration with
h) Can be adjusted from: 1 to 255 Hours;
i) Press
next parameter.
6.2.5.28 Auxiliary Relays settings
Program auxiliary output relays (dry contact). To locate the relays on the board, see
AUX 1 and AUX 2 at NXT2 controller connections [}Page 54].
Info
The NXT2 has two auxiliary relays available based on alarm, cycle, time or volume.
The following settings are auxiliary 1 settings and are the same for auxiliary 2.
Options:
• standby (activates relay from beginning of regeneration and during standby
phase);
• off;
• alarm based;
• cycle based;
• time based;
• volume based.
a) Choose the options of relay with
b) Default setting: disabled;
c) Press
next parameter.
Ref. MKT-IM-010 / C - 18.10.2019
Installer manual Fleck 3150 NXT/NXT2 - Programming
to validate the selection and advance to the
,
and ;
to validate the selection and advance to the
and
to validate the selection and advance to the
to validate the selection and advance to the
and
;
;
and
;
Continuous flow detect
activated.
Continuous flow detect -
Flow rate 0.1 l/min.
Continuous flow detect -
Duration 8H.
Disabled.
111 / 182