6.1.5.17 Regeneration start time
Set the time for regeneration start.
Info
It must be set when the valve is in timeclock mode or with a calendar override.
a) Adjust the time of regeneration with
b) Press
next parameter.
6.1.5.18 Programming regeneration cycle times
Set the cycle times of the regeneration.
Info
Five cycles can be set. The system displays the programming cycles. The display allows
setting of a specific time for each cycle. If a cycle is set to NO, the next cycles is not
activated.
Info
The sequence of the regeneration cycles depends upon regenerant flow, see System
regeneration cycle [}Page 20].
a) Adjust the cycle time with
b) Press
next parameter.
c) Repeat for each cycle.
74 / 182
to validate the selection and advance to the
,
to validate the selection and advance to the
,
and
.
Regeneration at 2:00 am.
and
.
1. Backwash: 10 min.
2. Draw/Slow rinse:
1 h 10 min.
3. Fast rinse: 10 min.
4. Refill: 10 min.
5. Pause: not used.