WARNING
MAIN AC POWER DISCONNECT
You must install an AC power disconnect for the entire
rack unit. This main disconnect must be readily
accessible, and it must be labeled as controlling power to
the entire unit, not just to the Succession Signaling
Server(s).
Damage to Equipment
OVERCURRENT PROTECTION
The Succession Signaling Server is designed for an AC
line voltage source with up to 20 amperes (A) of
over-current protection. If the power system for the
equipment rack is installed on a branch circuit with more
than 20 A of protection, provide supplemental protection
for the Succession Signaling Server. If more than one
Succession Signaling Server is installed in the rack, the
power source for each Succession Signaling Server
must be from a separate branch circuit.
Procedure 2
Rack-mounting the Succession Signaling Server
1
Attach the rack-mount brackets ('B' as shown in Figure 5 on
the equipment rack. Install the left and right side at an equal height. Use
standard length screws from the accessories pouch, and screw them into
the top and bottom drill holes of the bracket. See Figure 10 on
Hardware installation
Signaling Server
Installation and Configuration
Page 41 of 116
page
36) to
page
42.