Diagnostic ACE, to change LED to "Inputs displayed".
Do not hold button down.
If TurfDefender is functioning normally:
1. When the "Inputs displayed" LED is lit, the actual
Float position (1 or 2 LED's on left row) and "Oil level
OK" LED – should be displayed.
2. Press toggle button until green "Outputs displayed"
LED is lit. "Valve ON", "data line" and "self diagnos-
tic"LED's should be lit steadily. "Alarm ON" LED may be
displayed temporarily (about 5 seconds).
Note: If "data line" or "self diagnostic" LED's are blink-
ing, there is a problem in the system.
If No beeps are heard:
1. Check alarm wires to make sure they are not dis-
connected, broken or "+" and "–" reversed.
2. Make sure TurfDefender 4–pin connector is
plugged in.
3. Make sure TurfDefender 5 amp fuse (fuse block "B",
slot #3) is not blown.
4. Toggle "outputs displayed" on Diagnostic ACE dis-
play.
D
Alarm open circuit (LED blinking): Check / re-
place TurfDefender alarm or wires.
D
Alarm short circuit (LED blinking): Check / re-
place TurfDefender alarm or wires.
If 4 beeps are heard:
The most common cause for a 4 beep signal is from an
improper oil level reading. Make sure machine is on a
level surface when checking oil level. Since oil level will
vary with temperature, it is best to check when cool.
1. When toggling "input", a LED should display any of
the following problems diagnosed by the TurfDefender:
D
Oil level low: Position machine on a level surface
and fill to proper level.
D
Oil level high: Position machine on a level sur-
face and remove excess oil until proper level is at-
tained.
Electrical System
D
Oil too hot: Allow machine to cool and clean any
debris from oil cooler.
D
Air leak in system: Assure tank cap is tight or
check for leak in tank.
Note: Only large air leaks can be detected by hand
held Diagnostic ACE. A leak down test is required to
identify small air leaks. Consult your Authorized Toro
Distributor for assistance.
2. When toggling "output" a LED should display any of
the following problems diagnosed by the TurfDefender:
D
Valve open circuit (LED blinking): Check / re-
place TurfDefender electric solenoid valve or wires.
D
Valve short circuit (LED blinking): Check / re-
place TurfDefender electric solenoid valve or wires.
D
Self diagnostic LED Blinking: Internal circuit fail-
ure in TurfDefender. Consult your Authorized Toro
Distributor for assistance.
D
Data Line LED Blinking: Problem with commu-
nications between machine and leak detector; or
problem with wires. Consult your Authorized Toro
Distributor for assistance.
Note: If machine must be operable with leak detector
disabled, unplug leak detector 4–pin connector from
4–pin connector of main harness. Do not unplug leak
detector alarm.
1
Page 5 – 26.2
Rev. B
Figure 11b
1. Electric solenoid valve
Reelmaster 6500–D/6700–D