Thermal And Cooling Requirements; Servicing Requirements - Western Digital OpenFlex F3100 User Manual

Hide thumbs Also See for OpenFlex F3100:
Table of Contents

Advertisement

User Guide
Static Load Rating
Dynamic Load Rating
1.6.3   Thermal and Cooling Requirements
The thermal output of the OpenFlex F3100 and E3000 depends on the number of F3100s that are
populated in the E3000. Use the following table to determine how many BTUs of heat will exhaust from the
rear of the unit.
Table 20: BTU Exhaust per Component
Condition
Single E3000 w/ BMC Module
Single F3100
E3000 Fully Populated with
F3100s
1.6.4   Servicing Requirements
Space Requirements
The installation of the OpenFlex F3100 and E3000 will require enough space in front of the rack for two
people to perform a safe installation. The recommended forward clearance is 889 mm / 35 in. from the
front of the rack and 609.6 mm / 24 in. on both sides of the enclosure. It is also recommended to make
considerations for any carts or lift equipment that might be used to perform the installation.
of the enclosure requires one person and a minimum of 508 mm / 20 in. of space in front of the rack to
allow enough clearance to remove an F3100 from the enclosure. See the following diagram for details.
* The weight of the enclosure during installation will vary, depending on the number of F3100 devices and blanks
contained in the E3000. In some situations, carts or lift equipment may be required.
Parameter
Typical BTU Output
768 BTU/hr = 225 W
(25C/77F, fans at 50%)
409 BTU/hr = 120 W
(25C/77F, Workload: Random
Read/Write, queue depth
32, 80% internal processors
dedicated to workload)
5244 BTU/hr = 1537 W
(25C/77F, fans at 50%)
Requirement
Rack meets ISTA 3E or 3B test requirements and
regulations when mounted to the shipping pallet
Rack meets ISTA 3E or 3B test requirements and
regulations when mounted to the shipping pallet
1177 BTU/hr = 345 W
(35C/95F, fans at 100%)
546 BTU/hr = 160 W
(35C/95F, workload: Highest
throughput to drives – Seq
Write, queue depth 32, all
internal processors at 100%)
5884 BTU/hr = 1725 W
(35C/95F, fans at 100%)
1. Overview
1.6 Site Requirements
Max BTU Output
The servicing
 *
18