Backing Up Settings - Omron NX701-17 Series User Manual

Nj/nx-series, machine automation controller, cpu unit built-in ethercat port
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

9 Troubleshooting
9-4-3

Backing Up Settings

Before you replace an EtherCAT slave that is currently performing communications, the settings of the
EtherCAT slave to replace are backed up. The settings of an EtherCAT slave are divided according to
the storage locations and setting methods into initial parameters and backup parameters, as shown in
the following table.
Slave settings
Initial parameters
Backup parameters
To replace an EtherCAT slave, you first back up the backup parameters that are stored in the EtherCAT
slave.
1
Click the Edit Backup Parameter Settings Button in the EtherCAT Slave Setting Tab Page.
The Backup Parameter Settings Tab Page is displayed.
2
Click the Transfer from Slave Button.
All of the backup parameters that are stored in the EtherCAT slave and displayed in the list are
transferred from the EtherCAT slave.
3
Click the Compare Button.
Check to be sure that you have correctly obtained the backup parameters in step 2.
9-70
Storage location
EtherCAT master
These parameters are set automatically from the EtherCAT
master when EtherCAT communications start or when a
slave is connected.
EtherCAT slaves
You set these parameters by transferring them to the slaves
from the Backup Parameter Settings Tab Page of the Sys-
mac Studio.
The data can also be transferred from the EtherCAT Drive
Tab Page.
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
Slave setting method

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents