9 Troubleshooting
Examples of Finding Error Locations
Example 1: Network Configuration Where an EtherCAT Junction Slave Is Not Used
Network configuration
NJ/NX-series CPU Unit
EtherCAT master
(C)
(A)
(B)
IN
OUT
IN
OUT
IN
OUT
IN
OUT
Slave
Slave
Slave
Slave
node address 64
node address 3
node address 4
node address 5
Slave Diagnosis/Statistics Tab Page
The number of error frames for the input port (PortA) for node address 4 is 31, so you can see
that error frames were received on the input port for node address 4.
9
Therefore, you can assume that there is a problem between the output port (PortB) for node
address 3 and the input port for node address 4.
This corresponds to location (A), (B) or (C) in the network configuration diagram.
Concretely, you can assume the following possible error locations.
• The device at node address 3
• The cable between the output port at node address 3 and the input port at node address 4 or
the connectors at those ports
• The device at node address 4