Advertisement

Event code
Event name
842F0000 hex
Input Pro-
(Ver. 1.13 or
cess Data
later)
Invalid Error
102F 0000 hex
EtherCAT
(Ver. 1.03 or
Slave
later)
Backup
Failed
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
Meaning
Assumed cause
Because the Ether-
• Hardware failure of EtherCAT
CAT master could
slave
not perform pro-
• Noise
cess data commu-
nications normally
when it was in the
Operational state,
the Input Data
Invalid state contin-
ued for the follow-
ing period.
• When the task
period is 10 ms or
shorter: 100 ms
• When the task
period is longer
than 10 ms: 10
periods of the
task
The backup opera-
• There is no connection
tion for an Ether-
between the EtherCAT master
CAT slave ended in
and the slave (Link OFF).
an error.
• An error caused an incorrect
EtherCAT master status.
• The EtherCAT network configu-
ration information does not
agree with the physical network
configuration.
• The request to the EtherCAT
slave failed.
• The EtherCAT master was tem-
porarily unable to perform the
processing because it was exe-
cuting other processing.
• Initialization of the EtherCAT
slave failed.
• It was not possible to read the
backup parameters from the
EtherCAT slave.
• Communications with an
OMRON Communications Cou-
pler Unit or NX Unit failed.
9 Troubleshooting
Level
Maj
Prt
Min
Obs Info
page 9-35
page 9-36
Reference
9
9-13