Omron NX701-17 Series User Manual page 234

Nj/nx-series, machine automation controller, cpu unit built-in ethercat port
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

9 Troubleshooting
The file name, file type and save location of the log file saved in the SD Memory Card are given
below.
Item
File name
File format
Save location
Additional Information
The following available space is required in an SD Memory Card to save the diagnostic and sta-
tistical information.
Size of a data = 273 bytes + 51 bytes × Number of EtherCAT slaves
If the number of EtherCAT slaves is 512 and you want to save 1,000 diagnostic and statistical
data, an available space of approximately 26 MB is required.
The specification of data saved in a log file is given below.
• For the first row, data are output in the following order: the CPU Unit model, software version,
package version, hardware version, and serial ID. For the following rows, the date and time of
acquisition and the diagnostic and statistical data are output.
• The number of error frames for the slave diagnostic and statistical information is left blank if the
number of error frames cannot be acquired from the relevant EtherCAT slave.
Additional Information
The items of information such as the master diagnostic and statistical information output to a
CSV file by this function are arranged in the same order as the diagnostic and statistical informa-
tion display of Sysmac Studio. You can make the same file format by exchanging the places of
the row and column of each item.
 Related System-defined Variables
The following system-defined variables are used to control execution of the diagnosis/statistics log.
Refer to 7-1-2 System-defined Variables for details on system-defined variables.
_EC_StatisticsLogEnable
_EC_StatisticsLogCycleSec
_EC_StatisticsLogBusy
_EC_StatisticsLogErr
 Procedures
The procedure to use the diagnosis/statistics log is as follows.
1
Set a value for _EC_StatisticsLogCycleSec (Diagnosis/Statistics Log Cycle).
The cycle to save the diagnostic and statistical information in a log file is set.
Set the value in units of seconds. (Example: set 30 for 30 seconds, set 1,800 for 30 minutes).
If 0 is set, the diagnostic and statistical information is saved only once when execution of this
function is completed.
9-64
Specifications
ECAT_STATISTICS.csv
CSV
Root folder
Variable name
Meaning
Diagnosis/Statistics Log Enable
Diagnosis/Statistics Log Cycle
Diagnosis/Statistics Log Busy
Diagnosis/Statistics Log Error
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents