Event name
Process Data Reception Timeout
Meaning
Process data reception timed out.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
_EC_PDTimeoutErr
Cause and
Assumed cause
correction
The Ethernet cable is broken or the
specified cable is not being used.
A connector on the Ethernet cable is
disconnected, the contact is faulty, or
parts are faulty.
A general-purpose Ethernet hub is
connected.
The master failed.
The slave failed.
The Ethernet cable is too long.
The CPU Unit task period is too short.
Noise
Attached
Attached Information 1: Error Details
information
Precautions/
None
Remarks
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
Source details
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
Flashes at 1-s intervals.
Data type
BOOL
Correction
The causes given on the left are pos-
sible if the error occurs from when the
system starts operation or if it always
occurs after a specific time after the
system starts operation. Use the diag-
nostic and statistical information from
the Sysmac Studio and check the
EtherCAT communications status. If
the Ethernet cable between the mas-
ter and slave is broken or if the speci-
fied cable was not used, replace the
cable. Or, reconnect the connector
and make sure it is mated correctly. If
a general-purpose Ethernet hub is
connected, replace it with an Ether-
CAT Junction Slave. If the CPU Unit
or an EtherCAT slave fails, replace it.
The causes given on the left are pos-
sible if the error occurs from when the
system starts operation. If the Ether-
net cable is too long, shorten it. If the
error still occurs, connect the Sysmac
Studio, increase the task period of the
primary periodic task or priority-5 peri-
odic task, and reconfigure the Con-
troller.
If this error occurs irregularly, imple-
ment noise countermeasures.
0001 hex: Occurred in the primary periodic task.
0002 hex: Occurred in the priority-5 periodic task.
9 Troubleshooting
Event code
842B0000 hex
Master
Detection
timing
Error reset
Log category
When Fail-soft Operation Is Set to Fail-soft
Master:
Operation continues.
Slave:
Errors only occur in synced slaves. Operational state con-
tinues. Safe-operational state is entered if the state transi-
tion is made at the slave.
When Fail-soft Operation Is Set to Stop
Master:
All slaves enter the Pre-operational state.
Slave:
Errors only occur in synced slaves.
EtherCAT LINK/ACT
---
Name
Process Data Reception Timeout
Prevention
Make sure that the cable is not bro-
ken and use the specified cable.
Confirm that the Ethernet cable con-
nector is mated securely.
When branching an EtherCAT net-
work, use an EtherCAT Junction
Slave.
None
None
Make the Ethernet cable as short as
possible.
If there is a large number of EtherCAT
slaves connected, increase the task
period of the primary periodic task or
priority-5 periodic task .
Implement noise countermeasures.
During communi-
cations
System
9
9-33

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents