9 Troubleshooting
Attached
Attached Information 1: Error Details (The following values are in the order of the causes of the error.)
information
0001 hex: Link OFF
0002 hex: Incorrect master status
0003 hex: Configuration information does not agree with network configuration.
0004 hex: The request to the EtherCAT slave failed.
0005 hex: Master status temporarily prevented processing.
0006 hex: An error occurred in slave initialization.
0007 hex: Writing the backup data failed.
0008 hex: The backup data is not correct.
0009 hex: The network configuration does not agree with the network configuration in the backup data.
000A hex: The service is not supported
000B hex: Error at OMRON Communications Coupler Unit
Attached Information 2: Error Location
0: Master
1 or higher: Slave node address
Attached Information 3: Error Location Details (only when attached information 1 is 000B hex).
0: Communications Coupler Unit
1 to 63: Unit number of NX Unit
Attached Information 4: Cause of Error at OMRON Communications Coupler Unit (only when attached information 1 is
000B hex).
1: Reading the backup file failed.
2: Communications with the Communications Coupler Unit or NX Unit failed.
3: The Unit Configuration does not agree with the Unit Configuration in the backup data.
Precautions/
None
Remarks
* This event code occurs for unit version 1.03 or later of the CPU Unit.
Event name
Emergency Message Detected
Meaning
An emergency message was detected.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
_EC_SlavEmergErr
Cause and
Assumed cause
correction
An emergency message was
received from a slave.
Attached
Attached Information 1: Slave emergency code
information
Attached information 2: Slave error register object value
Attached Information 3: Slave emergency data. Only the lower five bytes are valid.
Precautions/
None
Remarks
9-40
Source details
Observation
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
BOOL
Correction
Clear the error from the EtherCAT
slave where the application error
occurred. Use the procedure given in
the slave documentation.
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
Event code
64200000 hex
Slave
Detection
timing
---
Log category
Slave:
An error occurred. Other operation is not affected.
EtherCAT LINK/ACT
---
Name
Emergency Message Detected
Prevention
Refer to the information given in the
manual for the slave and implement
countermeasures to prevent the prob-
lem.
During communi-
cations
System