 Step 5: Confirming After Implementing Corrections
To confirm that the error locations were corrected, perform Step 2: Checking for Errors in Trends in
Master Diagnostic and Statistical Information on page 9-51 again to make sure the network is oper-
ating normally.
Diagnostic and Statistical Information Display of Sysmac Studio
This section describes how to activate the diagnostic and statistical information display of Sysmac Stu-
dio. The functions of the operation buttons and displayed items are also explained.
 Activation
Activate the diagnostic and statistical information display of Sysmac Studio as follows.
1
Start the Sysmac Studio and go online with the Controller.
2
Double-click EtherCAT under Configurations and Setup in the Multiview Explorer. Or, right-
click EtherCAT under Configurations and Setup and select Edit.
3
Right-click the EtherCAT master on the EtherCAT Tab Page and select Display
Diagnosis/Statistics Information from the menu.