Event name
Slave Disabled
Meaning
The EtherCAT Slave was disabled.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
_EC_PDSlavTbl
_EC_DisableSlavTbl
Cause and
Assumed cause
correction
The EC_ChangeEnableSetting
instruction was executed.
Attached
None
information
Precautions/
None
Remarks
*1 This event code occurs for unit version 1.04 or later of the CPU Unit.
*2 "n" is 512 for an NX-series CPU Unit and 192 for an NJ-series CPU Unit.
Event name
Slave Enabled
Meaning
The EtherCAT Slave was enabled.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
_EC_PDSlavTbl
_EC_DisableSlavTbl
Cause and
Assumed cause
correction
The EC_ChangeEnableSetting
instruction was executed.
Attached
None
information
Precautions/
None
Remarks
*1 This event code occurs for unit version 1.04 or later of the CPU Unit.
*2 "n" is 512 for an NX-series CPU Unit and 192 for an NJ-series CPU Unit.
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
Source details
Information
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
Array[1..n] of BOOL
Array[1..n] of BOOL
Correction
---
Source details
Information
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
Array[1..n] of BOOL
Array[1..n] of BOOL
Correction
---
9 Troubleshooting
Event code
94440000 hex
Slave
Detection
timing
---
Log category
Master:
Process data communications stop for the slave.
Slave:
Enters the Pre-operational state. It will be possible to set
parameters. Process data communications are not possi-
ble.
EtherCAT LINK/ACT
---
Name
*2
Process Data Communicating Slave
Table
*2
Disabled Slave Table
Prevention
---
Event code
94450000 hex
Slave
Detection
timing
---
Log category
Master:
The slave enters the Operational state again, and process
data communications restart.
Slave:
Enters the Operational state.
EtherCAT LINK/ACT
---
Name
*2
Process Data Communicating Slave
Table
*2
Disabled Slave Table
Prevention
---
*1
At execution of
setting instruction
System
*1
At execution of
setting instruction
System
9
9-45

Advertisement

Table of Contents

Troubleshooting

loading