Omron NX701-17 Series User Manual page 159

Nj/nx-series, machine automation controller, cpu unit built-in ethercat port
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

7 System-defined Variables That Are Related to the Built-in EtherCAT Port
Variable name
_EC_CommErrTbl
Meaning
Communications Error Slave Table
Function
Slaves are given in the table in the order of slave node addresses.
The corresponding slave element is TRUE if the master detected an error for the slave.
Data type
Array [1..512] OF BOOL
R/W access
R
Usage in user program
Possible.
* For the NX1P2 CPU Units and NJ-series CPU Units, the data type is Array [1..192] OF BOOL.
Note The values of all system-defined variables that are related to errors in EtherCAT communications do not change until the
cause of the error is removed and then the error in the Controller is reset with the troubleshooting functions of the Sys-
mac Studio or the ResetECError instruction.
Variable name
_EC_CycleExceeded
Meaning
EtherCAT Communications Cycle Exceeded
Function
TRUE if the CPU unit cannot establish communications within the set communications period at startup.
Note You can use this system-defined variable only for NX-series CPU Units.
Data types
BOOL
R/W access
R
Usage in user program
Possible.
 Functional Classification: EtherCAT Communications Status
Variable name
_EC_RegSlavTbl
Meaning
Registered Slave Table
Function
This table indicates the slaves that are registered in the network configuration information.
Slaves are given in the table in the order of slave node addresses.
The element for a slave is TRUE if the corresponding slave is registered.
Data type
Array [1..512] OF BOOL
R/W access
R
Usage in user program
Possible.
* For the NX1P2 CPU Units and NJ-series CPU Units, the data type is Array [1..192] OF BOOL.
Variable name
_EC_EntrySlavTbl
Meaning
Network Connected Slave Table
Function
This table indicates which slaves are connected to the network.
Slaves are given in the table in the order of slave node addresses.
The element for a slave is TRUE if the corresponding slave has entered the network.
Data type
Array [1..512] OF BOOL
R/W access
R
Usage in user program
Possible.
* For the NX1P2 CPU Units and NJ-series CPU Units, the data type is Array [1..192] OF BOOL.
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
*
Retained
Not retained.
Related instruc-
Reset EtherCAT Error
tions
• ResetECError
Retained
Not retained.
Related instruc-
---
tions
*
Retained
Not retained.
Related instruc-
---
tions
*
Retained
Not retained.
Related instruc-
---
tions
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
7
7-13

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents