9 Troubleshooting
Event name
EtherCAT Fault
Meaning
A fatal error was detected in the EtherCAT Master Function Module.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Software is corrupted.
Attached
Attached information 1: System information 1
information
Attached information 2: System information 2
Attached information 3: System information 3
Attached information 4: System information 4
Precautions/
None
Remarks
9-18
Source details
Partial fault
Recovery
Continues.
Operation
EtherCAT NET ERR
Lights.
Data type
---
Correction
Replace the CPU Unit.
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
Event code
44010000 hex
Master
Detection
timing
Cycle the power
Log category
supply or reset
the Controller.
Master:
The EtherCAT Master Function Module stops.
Slave:
Parameter setting is not possible. Process data communi-
cations are not possible.
If the error occurred during synchronized communications
between the master and slave, then the error occurred at
the slave. The error is processed according to settings in
the slave.
EtherCAT LINK/ACT
---
Name
---
Prevention
None
During communi-
cations
System