9 Troubleshooting
Example 2: Network Configuration Where an EtherCAT Junction Slave Is Used
Network configuration
NJ/NX-series CPU Unit
EtherCAT master
node address 64
Slave Diagnosis/Statistics Tab Page
The number of error frames for the input port (PortA) for node address 4 is 123, so you can see
that error frames were received on the input port for node address 4.
Therefore, you can assume that there is a problem between the output port (X3) for node
address 64 and the input port for node address 4.
This corresponds to location (A), (B) or (C) in the network configuration diagram.
Concretely, you can assume the following possible error locations.
• The device at node address 64
• The cable between the output port at node address 64 and the input port at node address 4 or
the connectors at those ports
• The device at node address 4
9-54
IN
OUT
Junction slave
(A)
(B)
(C)
IN
OUT
Slave
node address 3
IN
OUT
IN
Slave
Slave
node address 4
node address 5
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)