9 Troubleshooting
Event name
EtherCAT Communications Cycle Exceeded
Meaning
Process data communications could not be performed with the specified communications cycle.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
_EC_CycleExceeded
Cause and
Assumed cause
correction
The transmission delay time in the
actually connected configuration is
longer than the transmission delay
time calculated for the user-set cable
length.
The set task period or communica-
tions cycle is too short.
Attached
None
information
Precautions/
None
Remarks
* This event code occurs for unit version 1.10 or later of the CPU Unit.
Event name
Controller Insufficient Memory Warning
Meaning
The amount of data for the EtherCAT slave configuration, network-published information, or other data exceeds the
value that is specified for the CPU Unit. You may not be able to perform online editing or other operations.
Source
EtherCAT Master Function Module or
EtherNet/IP Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The amount of data for the EtherCAT
slave configuration, network-pub-
lished information, or other data
exceeds the value that is specified for
the CPU Unit.
Attached
None
information
Precautions/
You may not be able to perform online editing or other operations.
Remarks
* This event code occurs for unit version 1.02 or later of the CPU Unit.
9-24
Source details
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
Flashes at 1-s intervals.
Data type
BOOL
Correction
Set the cable length so that it agrees
with the actual configuration.
Use the Simulator and set a task
period (communications cycle) that
enables communications.
Source details
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
---
Correction
Reduce the number of PDOs that are
used by the EtherCAT slaves.
Reduce the number of data types that
are used for network variables or
reduce the length of the text strings
that are used for names.
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
Event code
34410000 hex*
Master
Detection
timing
Automatic
Log category
recovery
Master:
The master waits in the Init state.
Slave:
Parameter setting is not possible. Process data communi-
cations are not possible.
EtherCAT LINK/ACT
---
Name
EtherCAT Communications Cycle
Exceeded
Prevention
Set the cable length so that it agrees
with the actual configuration.
Use the Simulator and set a task
period (communications cycle) that
enables communications.
Event code
50010000 hex*
Master or CIP
Detection
timing
Error reset
Log category
Not affected.
EtherCAT LINK/ACT
---
Name
---
Prevention
None
At start of com-
munications
System
At power ON,
download, or
online editing
System

Advertisement