Cause and
Communications with an OMRON
correction
Communications Coupler Unit or NX
Unit failed.
Attached
Attached Information 1: Error Details (The following values are in the order of the causes of the error.)
information
0001 hex: Link OFF
0002 hex: Incorrect master status
0003 hex: Configuration information does not agree with network configuration.
0004 hex: The request to the EtherCAT slave failed.
0005 hex: Master status temporarily prevented processing.
0006 hex: An error occurred in slave initialization or a slave is disconnected from the network.
0007 hex: Reading the backup data failed.
000B hex: Error at OMRON Communications Coupler Unit
Attached Information 2: Error Location
0: Master
1 or higher: Slave node address
Attached Information 3: Error Location Details (only when attached information 1 is 000B hex).
0: Communications Coupler Unit
1 to 63: Unit number of NX Unit
Attached Information 4: Cause of Error at OMRON Communications Coupler Unit (only when attached information 1 is
000B hex).
2: Communications with the Communications Coupler Unit or NX Unit failed.
Precautions/
None
Remarks
*1 This event code occurs for unit version 1.03 or later of the CPU Unit.
*2 "n" is 512 for an NX-series CPU Unit and 192 for an NJ-series CPU Unit.
NJ/NX-series CPU Unit Built-in EtherCAT Port User's Manual (W505)
Connect the cable securely.
Mount the NX Unit securely.
Implement noise countermeasures if
there is excessive ambient noise.
If the problem still exists, replace the
Communications Coupler Unit or the
NX Unit.
9 Troubleshooting
Connect the cable securely.
Mount the NX Unit securely.
Implement noise countermeasures if
there is excessive ambient noise.
9