D7: Offset Frequency - YASKAWA GA800 Programming Manual

Ac drive for industrial applications
Table of Contents

Advertisement

d7: Offset Frequency

No.
Name
(Hex.)
d7-01
Offset Frequency 1
(02B2)
RUN
d7-02
Offset Frequency 2
(02B3)
RUN
d7-03
Offset Frequency 3
(02B4)
RUN
YASKAWA TOEPYAIGA8002B GA800 Drive Programming
Description
V/f
CL-V/f
OLV
CLV
AOLV
Uses H1-xx = 44 [MFDI Function Select = Add Offset Frequency 1 (d7-01)] as a
percentage of the Maximum Output Frequency to add or subtract the set frequency to/from
the frequency reference.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Uses H1-xx = 45 [MFDI Function Select = Add Offset Frequency 2 (d7-02)] as a
percentage of the Maximum Output Frequency to add or subtract the set frequency to/from
the frequency reference.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
CL-V/f
OLV
CLV
AOLV
Uses H1-xx = 46 [MFDI Function Select = Add Offset Frequency 3 (d7-03)] as a
percentage of the Maximum Output Frequency to add or subtract the set frequency to/from
the frequency reference.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
1.7 d: Reference Settings
Default
Ref.
(Range)
0.0%
294
(-100.0 - +100.0%)
0.0%
294
(-100.0 - +100.0%)
0.0%
294
(-100.0 - +100.0%)
43
1

Advertisement

Table of Contents
loading

Table of Contents