Fan Unit Test
....................................................................................................................................................................................................................................
Overview
Procedure
....................................................................................................................................................................................................................................
365-374-059
Issue a, January 2002
This test clarifies the correct working of the Fan Unit in the
™
LambdaUnite
MultiService Switch (MSS) subrack. Check if the fan
unit is running. The test should be carried out for each installed NE.
Proceed as follows to test the correct functionality of the fan
unit:
............................................................................................................................................................
Control the correct installation of the fan unit and fan filter.
1
Check that
•
the air flow direction is from bottom to top
•
the unit is fixed correctly.
............................................................................................................................................................
2
Control the status indication on the faceplate of the fan unit.
Result:
On the fan unit only the PWR ON LED should be lit.
E
S
N D
O F
T E P S
.........................................................................................................................................................................................................................................................
Lucent Technologies
Test Procedures
6 - 5