Technical Data

....................................................................................................................................................................................................................................
Specifications
Item
Voltage Range (all components)
Power Feeders
Upstream Fuse or Circuit-Breaker
Power Consumption
Weight
Dimensions (D x W x H)
Site Engineering Dimensions
Subrack Requirements
....................................................................................................................................................................................................................................
3 - 4 8
Quantity/Value
-48 to -60 V battery voltage
(-40.5 V minimum, -72 V maximum)
Two power feeders (A, B)
The fuse must be ≥ 68 A in the external BDFB
(depends on cable)
2200 Watt maximum
(depends on configuration).
Maximum 41kg [90.41 lbs]
(includes: user panel, fan, PIs, CI-CTL TIs and 12x
blanks at the rear).
545mm [21.457"] x 500mm [19.685"] x 950mm
[37.402"]
(includes fan and cabling).
545mm [21.457"] x 500mm [19.685"] x 1100mm
[43.307"]
(includes cabling and fan space)
The mounting requirements are:
Leave a space of ≥ 100 mm [3,94"] above the subrack, when a
single subrack is mounted into a rack frame.
The subrack is designed for mounting in the LambdaUnite
Rack Frames so that the temperature can be controlled and the
cables laid properly.
Lucent Technologies
Equipment Installation
MSS
365-374-059
Issue a, January 2002