Technical Data
....................................................................................................................................................................................................................................
Specifications
Item
Voltage Range (all components)
Power Feeders
Upstream Fuse or Circuit-Breaker
Power Consumption
Weight
Dimensions (D x W x H)
Site Engineering Dimensions
Subrack Requirements
....................................................................................................................................................................................................................................
3 - 4 8
Quantity/Value
-48 to -60 V battery voltage
(-40.5 V minimum, -72 V maximum)
Two power feeders (A, B)
The fuse must be ≥ 68 A in the external BDFB
(depends on cable)
2200 Watt maximum
(depends on configuration).
Maximum 41kg [90.41 lbs]
(includes: user panel, fan, PIs, CI-CTL TIs and 12x
blanks at the rear).
545mm [21.457"] x 500mm [19.685"] x 950mm
[37.402"]
(includes fan and cabling).
545mm [21.457"] x 500mm [19.685"] x 1100mm
[43.307"]
(includes cabling and fan space)
The mounting requirements are:
•
Leave a space of ≥ 100 mm [3,94"] above the subrack, when a
single subrack is mounted into a rack frame.
•
The subrack is designed for mounting in the LambdaUnite
Rack Frames so that the temperature can be controlled and the
cables laid properly.
Lucent Technologies
Equipment Installation
™
MSS
365-374-059
Issue a, January 2002