Installation Troubleshooting; Power Failure - Lucent Technologies LambdaUnite Installation Manual

Multiservice
Hide thumbs Also See for LambdaUnite:
Table of Contents

Advertisement

Power Failure

....................................................................................................................................................................................................................................
Overview
Procedure 1
....................................................................................................................................................................................................................................
7 - 2
The procedures described below should be performed if the subrack
powering procedure was unsuccessful.
Procedure 1 should be used if the measured voltage at the termination
blocks of the PDP does not lie between -40.5 and -72 V.
Procedure 2 should be used if the PWR ON LEDs do not light up on
the user panels.
Procedure 3 should be used if the PWR ON LEDs do not light up on
the fan units.
Follow the steps below if the measured voltage at the termination
blocks of the PDP does not lie between -40.5 and -72 V:
............................................................................................................................................................
Switch off the external battery.
1
............................................................................................................................................................
Replace all affected power supply lines between the external battery
2
and the termination blocks of the PDP. Make sure the cables are tight
afterwards.
..........................................................................................................................................................
Switch on the external battery.
3
IF ...
the measured voltage does
not lie between -40.5 and
-72 V,
the measured voltage lies
between -40.5 and -72 V,
E
S
N D
O F
T E P S
............................................................................................................................................................
Lucent Technologies

Installation Troubleshooting

THEN ...
check the external battery.
END OF STEPS
365-374-059
Issue a, January 2002