Table 24: Cabinet Requirements and Specifications

Cabinet
Requirement
Guidelines
Cabinet size
You can mount the device in a cabinet that contains a 19-in. rack as defined in Cabinets, Racks,
Panels, and Associated Equipment (document number EIA-310–D) published by the Electronics
Industry Association (
The minimum cabinet size must be able to accommodate the maximum external dimensions of the
device.
Cabinet clearance
The outer edges of the mounting brackets extend the width of the chassis to 19 in. (48.2 cm).
The minimum total clearance inside the cabinet is 30 in. (76.2 cm) between the inside of the front
door and the inside of the rear door.
Cabinet airflow
When you mount the device in a cabinet, ensure that ventilation through the cabinet is sufficient to
requirements
prevent overheating.
Ensure adequate cool air supply to dissipate the thermal output of the device or devices.
Ensure that the hot air exhaust of the chassis exits the cabinet without recirculating into the device.
An open cabinet (without a top or doors) that employs hot air exhaust extraction from the top
ensures the best airflow through the chassis. If the cabinet contains a top or doors, perforations in
these elements assist with removing the hot air exhaust.
Install the device in the cabinet in a way that maximizes the open space on the side of the chassis
that has the hot air exhaust.
Route and dress all cables to minimize the blockage of airflow to and from the chassis.
Ensure that the spacing of rails and adjacent cabinets is such that there is proper clearance around
the device and cabinet.
A cabinet larger than the minimum required provides better airflow and reduces the chance of
overheating.
Related
Documentation

Clearance Requirements for Airflow and Hardware Maintenance for OCX1100 Switches

Copyright © 2017, Juniper Networks, Inc.
Cabinet airflow requirements
Table 24 on page 37
provides the cabinet requirements and specifications.
http://www.ecianow.org/standards-practices/standards/
Rack-Mounting and Cabinet-Mounting Warnings on page 148
When planning the site for installing an OCX1100 switch, you must ensure sufficient
clearance around the switch.
Follow these clearance requirements:
Chapter 5: Preparation Overview
).
37