Hitachi WJ200-001S Instruction Manual page 478

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Standard Functions
NOTE:. Mark "" in A line of [ Run Mode Edit] shows the accessible parameters when b031 is not set "10",
high level access.
NOTE:. Mark "" in B line of [ Run Mode Edit] shows the accessible parameters when b031 is set "10",
high level access
Func.
Name
Code
Frequency source

Frequency source,

2
motor
nd
Run command source

Run command source,

2
motor
nd
Base frequency

Base frequency,

2
motor
nd
Maximum frequency

Maximum frequency,

2
motor
nd
[AT] selection

[O] input active range start

frequency
[O] input active range end

frequency
[O] input active range start

voltage
[O] input active range end

voltage
[O] input start frequency

enable
"A" Function
Description
Eight options; select codes:
 POT on ext. operator
 Control terminal
 Function F001 setting
 Modbus network input
 Option
 Pulse train input
 via EzSQ
 Calculate function output
Four options; select codes:
 Control terminal
 Run key on keypad,
or digital operator
 Modbus network input
 Option
Settable from 30 Hz to the maximum
frequency()
Settable from 30 Hz to the 2
frequency()
Settable from the base
frequency to 400 Hz
Settable from the 2
nd
frequency to 400 Hz
Three options; select codes:
...Select between [O] and [OI] at [AT]
(ON=OI, OFF=O)
...Select between [O] and external POT
at [AT]
(ON=POT, OFF=O)
...Select between [OI] and external
POT at [AT]
(ON=POT, OFF=OI)
The output frequency corresponding to
the analog input range starting point,
range is 0.00 to 400.0
The output frequency corresponding to
the analog input range ending point,
range is 0.0 to 400.0
The starting point (offset) for the active
analog input range,
range is 0. to 100.
The ending point (offset) for the active
analog input range,
range is 0. to 100.
Two options; select codes:
Use offset ( value)
Use 0Hz
Run
Mode
Edit
A
 
 
 
 
 
nd
maximum
 
 
base
 
 
Ver.249
Defaults
B
Initial data
Units
01
01
01
01
50.0
Hz
50.0
Hz
50.0
Hz
50.0
Hz
00
0.00
Hz
0.00
Hz
0.
%
100.
%
01

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents