Hitachi WJ200-001S Instruction Manual page 298

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

The [AM] signal offset and gain are adjustable, as indicated below.
Func.

[AM] output gain

[AM] output offset
The graph below shows the effect of the gain and offset setting. To calibrate the [AM]
output for your application (analog meter), follow the steps below:
1. Run the motor at the full scale speed, or most common operating speed.
a. If the analog meter represents output frequency, adjust offset () first, and
then use
b. If [AM] represents motor current, adjust offset () first, and then use
set the voltage for full scale output. Remember to leave room at the upper end of
the range for increased current when the motor is under heavier loads.
AM output offset adjustment
AM output
10V
=0~10
5V
0
NOTE: As mentioned above, first adjust the offset, and then adjust the gain. Otherwise
the required performance cannot be obtained because of the parallel movement of the
offset adjustment.
Description
to set the voltage for full scale output.

Parallel
movement
Full scale (FS)
1/2 FS
Hz or A
Range
Default
0.~255.
100.
0.0~10.0
0.0
AM output gain adjustment
AM output
10V
5V
0
1/2 FS
491
to

=0~255
Full scale (FS)
Hz or A