Func.
Name
Code
Curvature of EL-S-curve at

the end of deceleration
Deceleration hold frequency

Deceleration hold time

PID sleep function action

threshold
PID sleep function action

delay time
[VR] input active range start

frequency
[VR] input active range end

frequency
[VR] input active range

start %
[VR] input active range

end %
[VR] input start frequency

select
"A" Function
Description
Range is 0 to 50%
Sets the frequency to hold deceleration,
range is 0.0 to 400.0Hz
Sets the duration of deceleration hold,
range is 0.0 to 60.0 seconds.
Sets the threshold for the action, set
range 0.0 to 400.0 Hz
Sets the delay time for the action, set
range 0.0 to 25.5 seconds.
The output frequency corresponding to
the analog input range starting point,
range is 0.0 to 400.0 Hz
The output frequency corresponding to
the current input range ending point,
range is 0.0 to 400.0 Hz
The starting point (offset) for the current
input range,
range is 0. to 100.%
The ending point (offset) for the current
input range,
range is 0. to 100.%
Two options; select codes:
Use offset ( value)
Use 0Hz
Ver.255
Run
Mode
Defaults
Edit
A
B
Initial data
10.
 
0.00
0.0
0.00
0.0
0.00
0.00
0.
100.
01
Units
%
Hz
s
Hz
s
Hz
Hz
%
%