Connecting the Inverter to Modbus

Modbus connector is in control terminal block as below. Note that RJ45 connector
(RS-422) is used for external operator only.
SN
7
6
SP
EO
EA
RS-485
(Modbus)
External device
-
Terminate Network Wiring - The RS-485 wiring must be terminated at each physical
end to suppress electrical reflections and help decrease transmission errors. WJ200 has
a built-in 200
 resistor activated by a dip switch.
the characteristic impedance of the network cable. The diagram above shows a network
with the needed termination resistor at each end.
Dip switch for termination resistor
5
4
3
2
1
H
O
OI
L
AM
(Master)
+
SP
SN
200
WJ200 (No.1)
L
PLC P24
CM2
12
11
SP SN
WJ200 (No.2)
WJ200 (No.3)
Select termination resistors that match