Hitachi WJ200-001S Instruction Manual page 171

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

386
Option
Terminal
Code
Symbol

STA

STP

F/R

PID

PIDC

UP

DWN

UDC

OPE

SF1

SF2

SF3

SF4

SF5

SF6

SF7

OLR

TL

TRQ1

TRQ2
Input Function Summary Table
Function Name
Start
(3-wire interface)
Stop
(3-wire interface)
FWD, REV
(3-wire interface)
PID Disable
PID Reset
Remote Control UP
Function (motorized
speed pot.)
Remote Control Down
Function (motorized
speed pot.)
Remote Control Data
Clearing
Operator Control
Multi-speed Select,
Bit operation Bit 1
Multi-speed Select,
Bit operation Bit 2
Multi-speed Select,
Bit operation Bit 3
Multi-speed Select,
Bit operation Bit 4
Multi-speed Select,
Bit operation Bit 5
Multi-speed Select,
Bit operation Bit 6
Multi-speed Select,
Bit operation Bit 7
Overload Restriction
Source Changeover
Torque Limit Selection
Torque limit switch 1
Torque limit switch 2
Description
ON
Starts the motor rotation
OFF No change to present motor status
ON
Stops the motor rotation
OFF No change to present motor status
ON
Selects the direction of motor rotation: ON = FWD.
While the motor is rotating, a change of F/R will start
a deceleration, followed by a change in direction
OFF Selects the direction of motor rotation: OFF = REV.
While the motor is rotating, a change of F/R will start
a deceleration, followed by a change in direction
ON
Temporarily disables PID loop control. Inverter output
turns OFF as long as PID Enable is active (=)
OFF Has no effect on PID loop operation, which operates
normally if PID Enable is active (=)
ON
Resets the PID loop controller. The main
consequence is that the integrator sum is forced to zero
OFF No effect on PID controller
ON
Accelerates (increases output frequency) motor from
current frequency
OFF Output to motor operates normally
ON
Decelerates (decreases output frequency) motor
from current frequency
OFF Output to motor operates normally
ON
Clears the UP/DWN frequency memory by forcing it
to equal the set frequency parameter F001. Setting
 must be set= to enable this function to work
OFF UP/DWN frequency memory is not changed
ON
Forces the source of the output frequency setting
 and the source of the Run command  to be
from the digital operator
OFF Source of output frequency set by  and source
of Run command set by  is used
ON
Bit encoded speed select, Bit 1, logical 1
OFF Bit encoded speed select, Bit 1, logical 0
ON
Bit encoded speed select, Bit 2, logical 1
OFF Bit encoded speed select, Bit 2, logical 0
ON
Bit encoded speed select, Bit 3, logical 1
OFF Bit encoded speed select, Bit 3, logical 0
ON
Bit encoded speed select, Bit 4, logical 1
OFF Bit encoded speed select, Bit 4, logical 0
ON
Bit encoded speed select, Bit 5, logical 1
OFF Bit encoded speed select, Bit 5, logical 0
ON
Bit encoded speed select, Bit 6, logical 1
OFF Bit encoded speed select, Bit 6, logical 0
ON
Bit encoded speed select, Bit 7, logical 1
OFF Bit encoded speed select, Bit 7, logical 0
ON
Perform overload restriction
OFF Normal operation
Setting of  is enabled
ON
OFF Max. torque is limited with 200%
ON
Torque limit related parameters of Powering/regen,
and FW/RV modes are selected by the combinations
OFF
of these inputs.
ON
OFF

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents