Hitachi WJ200-001S Instruction Manual page 486

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Func.
Name
Code
Level of electronic thermal,

2
motor
nd
Electronic thermal

characteristic
Electronic thermal

characteristic, 2
motor
nd
Free setting electronic

thermal ~freq.1
Free setting electronic

thermal ~current1
Free setting electronic

thermal ~freq.2
Free setting electronic

thermal ~current2
Free setting electronic

thermal ~freq.3
Free setting electronic

thermal ~current3
Overload restriction

operation mode
Overload restriction

operation mode, 2
nd
Overload restriction level

Overload restriction level,

2
motor
nd
Deceleration rate at overload

restriction
Deceleration rate at overload

restriction, 2
nd
motor
Overload restriction

operation mode 2
Overload restriction level 2

Deceleration rate 2 at

overload restriction
OC suppression selection *

"b" Function
Description
rated inverter current.
Select from three curves, option codes:
Reduced torque
Constant torque
Free setting
Range is 0 to 400Hz
Range is 0 to inverter rated current Amps
Range is 0 to 400Hz
Range is 0 to inverter rated current Amps
Range is 0 to 400Hz
Range is 0 to inverter rated current Amps
Select the operation mode during
overload conditions, four options, option
codes:
motor
Disabled
Enabled for acceleration and
constant speed
Enabled for constant speed only
Enabled for acceleration and
constant speed, increase speed at
regen.
Sets the level of overload restriction,
between 20% and 200% of the rated
current of the inverter, setting resolution
is 1% of rated current
Sets the deceleration rate when inverter
detects overload, range is 0.1 to 3000.0,
resolution 0.1 seconds.
Select the operation mode during
overload conditions, four options, option
codes:
Disabled
Enabled for acceleration and
constant speed
Enabled for constant speed only
Enabled for acceleration and
constant speed, increase speed at
regen.
Sets the level of overload restriction,
between 20% and 200% of the rated
current of the inverter, setting resolution
is 1% of rated current
Sets the deceleration rate when inverter
detects overload, range is 0.1 to 3000.0,
resolution 0.1 seconds.
Two option codes:
Disabled
Enabled
Ver.257
Run
Mode
Defaults
Edit
A
B
Initial data
Units
current for
each
inverter
model *1
01
01
0.0
0.00
0.0
0.00
0.0
0.00
01
01
Rated
current
x 1.5
Rated
current
x 1.5
1.0
1.0
01
Rated
current
x 1.5
1.0
00
A
Hz
A
Hz
A
Hz
A
A
A
s
s
s