Hitachi WJ200-001S Instruction Manual page 640

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Func.
Func.
Func.
Func.
N N N N ame
ame
ame
ame
Code
Code
Code
Code
b b b b 0 0 0 0 4 4 4 4 6 6 6 6
Reverse run
protection
b b b b 0 0 0 0 4 4 4 4 9 9 9 9
Dual Rating
Selection
Controlled
b b b b 0 0 0 0 5 5 5 5 0 0 0 0
deceleration on
power loss
b b b b 0 0 0 0 5 5 5 5 1 1 1 1
DC bus voltage
trigger level of
ctrl. decel.
b b b b 0 0 0 0 52
52
52
52
Over-voltage
threshold of ctrl.
decel.
b b b b 0 0 0 0 53
53
53
53
Deceleration time
of ctrl. decel.
b b b b 0 0 0 0 54
54
54
54
Initial freq. drop
of ctrl. decel.
b b b b 0 0 0 0 6 6 6 6 0 0 0 0
Maximum-limit
level of window
comparator (O)
b b b b 0 0 0 0 6 6 6 6 1 1 1 1
Minimum-limit
level of window
comparator (O)
Hysteresis width
b b b b 0 0 0 0 6 6 6 6 2 2 2 2
of window
comparator (O)
b b b b 0 0 0 0 6 6 6 6 3 3 3 3
Maximum-limit
level of window
comparator (OI)
b b b b 0 0 0 0 6 6 6 6 4 4 4 4
Minimum-limit
level of window
comparator (OI)
Hysteresis width
b b b b 0 0 0 0 6 6 6 6 5 5 5 5
of window
comparator (OI)
b b b b 0 0 0 0 7 7 7 7 0 0 0 0
Operation level
at O
disconnection
Operation level
b b b b 0 0 0 0 7 7 7 7 1 1 1 1
at OI
disconnection
b b b b 0 0 0 0 7 7 7 7 5 5 5 5
Ambient
temperature
setting
b b b b 0 0 0 0 78
78
78
78
Watt-hour
clearance
b b b b 0 0 0 0 79
79
Watt-hour
79
79
display gain
Start frequency
b b b b 0 0 0 0 8 8 8 8 2 2 2 2
b b b b 0 0 0 0 8 8 8 8 3 3 3 3
Carrier frequency
b b b b 0 0 0 0 8 8 8 8 4 4 4 4
Initialization
mode
(parameters or
trip history)
Country for
b b b b 0 0 0 0 8 8 8 8 5 5 5 5
initialization
" " " " b b b b " " " " Function
Function
Function
Function
D D D D escription
Two option codes:
00
00
00 ... No protection
00
0 0 0 0 1 1 1 1 ... Reverse rotation is protected
00 ... (CT mode) / 0 0 0 0 1 1 1 1 ... (VT mode)
00
00
00
Four option codes:
00
00
00
00 ... Trips
0 0 0 0 1 1 1 1 ... Decelerates to a stop
0 0 0 0 2 2 2 2 ... Decelerates to a stop with DC bus voltage controlled
0 0 0 0 3 3 3 3 ... Decelerates to a stop with DC bus voltage controlled, then
restart
Setting of DC bus voltage to start controlled decel. operation.
Range is 0.0 to 1000.0
Setting the OV-LAD stop level of controlled decel. operation.
Range is 0.0 to 1000.0
Range is 0.01 to 3600.0
Setting of initial freq. drop.
Range is 0.00 to 10.00 Hz
Set range, {Min.-limit level (b b b b 0 0 0 0 6 6 6 6 1 1 1 1 ) + hysteresis width (b b b b 0 0 0 0 6 6 6 6 2 2 2 2 )x2}
to 100 %
(Minimum of 0%)
Set range, 0 to {Max.-limit level (b b b b 0 0 0 0 6 6 6 6 0 0 0 0 ) - hysteresis width
(b b b b 0 0 0 0 6 6 6 6 2 2 2 2 )x2} % (Maximum of 0%)
Set range, 0 to {Max.-limit level (b b b b 0 0 0 0 6 6 6 6 0 0 0 0 ) - Min.-limit level
(b b b b 0 0 0 0 6 6 6 6 1 1 1 1 )}/2 % (Maximum of 10%)
Set range, {Min.-limit level (b b b b 0 0 0 0 6 6 6 6 4 4 4 4 + hysteresis width (b b b b 0 0 0 0 6 6 6 6 5 5 5 5 )x2} to
100 %
(Minimum of 0%)
Set range, 0 to {Max.-limit level (b b b b 0 0 0 0 6 6 6 6 3 3 3 3 ) - hysteresis width
(b b b b 0 0 0 0 6 6 6 6 5 5 5 5 )x2} % (Maximum of 0%)
Set range, 0 to {Max.-limit level (b b b b 0 0 0 0 6 6 6 6 3 3 3 3 ) - Min.-limit level
(b b b b 0 0 0 0 6 6 6 6 4 4 4 4 )}/2 % (Maximum of 10%)
Set range, 0. to 100.%, or "no" (ignore)
Set range, 0. to 100.%, or "no" (ignore)
Set range is,
-10 to 50 ° C
Two option codes:
00
00 ... OFF
00
00
0 0 0 0 1 1 1 1 ... ON (press STR then clear)
Set range is,
1. to 1000.
Sets the starting frequency for the inverter output, range is 0.10
to 9.99 Hz
Sets the PWM carrier (internal switching frequency), range is
2.0 to 15.0 kHz
Select initialized data, five option codes:
00 ... Initialization disabled
00
00
00
0 0 0 0 1 1 1 1 ... Clears Trip history
0 0 0 0 2 2 2 2 ... Initializes all Parameters
0 0 0 0 3 3 3 3 ... Clears Trip history and initializes all parameters
0 0 0 0 4 4 4 4 ... Clears Trip history and initializes all parameters and EzSQ
program
0 0 0 0 1 1 1 1 ... Mode 1
escription
escription
escription
Ver.3− − − − 131
D D D D efaults
efaults
efaults
efaults
A A A A
B B B B
Initial data
Initial data
Initial data
Initial data
Units
Units
Units
Units
00
00
00
220.0/
V
440.0
360.0/
V
720.0
1.00
s
0.00
Hz
100.
%
0.
%
0.
%
100.
%
0.
%
0.
%
no
-
no
-
40
° C
00
-
1.
-
0.50
Hz
10.0
kHz
00
01