Hitachi WJ200-001S Instruction Manual page 404

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

Func.
Name
Code
Reverse run protection
b046
b049
Dual Rating Selection
Controlled deceleration on
B050
power loss
DC bus voltage trigger level
B051
of ctrl. decel.
Over-voltage threshold of
B052
ctrl. decel.
Deceleration time of ctrl.
B053
decel.
Initial freq. drop of ctrl.
B054
decel.
Maximum-limit level of
B060
window comparator (O)
Minimum-limit level of
B061
window comparator (O)
Hysteresis width of window
B062
comparator (O)
Maximum-limit level of
B063
window comparator (OI)
Minimum-limit level of
B064
window comparator (OI)
Hysteresis width of window
b065
comparator (OI)
Operation level at O
b070
disconnection
Operation level at OI
b071
disconnection
Ambient temperature setting
b075
Watt-hour clearance
B078
"b" Function
Description
Two option codes:
00...No protection
01...Reverse rotation is protected
00... (CT mode) / 01... (VT mode)
Four option codes:
00...Trips
01...Decelerates to a stop
02...Decelerates to a stop with DC
bus voltage controlled
03...Decelerates to a stop with DC
bus voltage controlled, then
restart
Setting of DC bus voltage to start
controlled decel. operation. Range
is 0.0 to 1000.0
Setting the OV-LAD stop level of
controlled decel. operation. Range
is 0.0 to 1000.0
Range is 0.01 to 3600.0
Setting of initial freq. drop.
Range is 0.0 to 10.0 Hz
Set range, {Min.-limit level (b061)
+ hysteresis width (b062)x2} to
100 %
(Minimum of 0%)
Set range, 0 to {Max.-limit level
(b060) - hysteresis width
(b062)x2} % (Maximum of 0%)
Set range, 0 to {Max.-limit level
(b060) - Min.-limit level (b061)}/2 %
(Maximum of 10%)
Set range, {Min.-limit level (b064 +
hysteresis width (b065)x2} to
100 %
(Minimum of 0%)
Set range, 0 to {Max.-limit level
(b063) - hysteresis width
(b065)x2} % (Maximum of 0%)
Set range, 0 to {Max.-limit level
(b063) - Min.-limit level (b064)}/2 %
(Maximum of 10%)
Set range, 0 to 100%, or "no"
(ignore)
Set range, 0 to 100%, or "no"
(ignore)
Set range is,
-10~50 °C
Two option codes:
00...OFF
01...ON (press STR then clear)
C− − − − 17
Run
Mode
Defaults
Edit
A
B
Initial data Units
00
00
00
220.0/
V
440.0
360.0/
V
720.0
1.00
sec
0.00
Hz
100.
%
0.
%
0.
%
100.
%
0.
%
0.
%
no
-
no
-
40
°C
00
-