Hitachi WJ200-001S Instruction Manual page 151

Wj200 series single/three-phase inputs 200v/400v class
Hide thumbs Also See for WJ200-001S:
Table of Contents

Advertisement

366
Func.
Code
Controlled deceleration on

power loss
DC bus voltage trigger

level of ctrl. decel.
Over-voltage threshold of

ctrl. decel.
Deceleration time of ctrl.

decel.
Initial freq. drop of ctrl.

decel.
"b" Function
Name
Four option codes:
Trips
Decelerates to a stop
Decelerates to a stop with DC
bus voltage controlled
Decelerates to a stop with DC
bus voltage controlled, then
restart
Setting of DC bus voltage to start
controlled decel. operation. Range
is 0.0 to 1000.0
Setting the OV-LAD stop level of
controlled decel. operation. Range
is 0.0 to 1000.0
Range is 0.01 to 3600.0
Setting of initial freq. drop.
Range is 0.0 to 10.0 Hz
Description
Run
Defaults
Mode
Initial data
Units
Edit
00
220.0/
V
440.0
360.0/
V
720.0
1.0
sec
0.0
Hz