Rack Mounting - Avaya IP500 V2 Installation Manual

Hide thumbs Also See for IP500 V2:
Table of Contents

Advertisement

4.7 Rack Mounting

All IP Office control units and external expansion modules can be rack mounted into standard 19" rack systems. Each unit
requires a 2U slot space within the rack. The IPO IP500 RACK MNTG KIT V3 is used for rack mounting of units.
Where IP Office systems are being rack mounted, the effect of conditions within the rack cabinet must be considered. For
example the rack temperature may be above the room temperature and airflow within the rack will be restricted. The
environmental requirements
Barrier Box Rack Mounting Kit
Environmental Requirements
In addition to the existing
considered when rack mounting a unit:
1. Rack Positioning - Ensure compliance with the rack manufacturers safety instructions. For example check that the
rack legs have been lowered and fixing brackets have been used to stop toppling.
2. Elevated Operating Ambient - If installed in a closed or multi-unit rack assembly, the operating ambient
temperature of the rack environment may be greater than room ambient. Therefore, consideration should be given
to installing the equipment in an environment compatible with the maximum ambient temperature (Tma) specified
by the manufacturer.
· o Operating Temperature: 5°C (40°F) to 40°C (104°F).
· o Operating Humidity: 10% to 95% non-condensing.
3. Reduced Air Flow - Installation of the equipment in a rack should be such that the amount of air flow required for
safe operation of the equipment is not compromised. Proper ventilation must be maintained. The side ventilation
slots on the IP500 control unit should not be covered or blocked.
4. Mechanical Loading - Mounting of the equipment in the rack should be such that a hazardous condition is not
achieved due to uneven mechanical loading.
5. Circuit Overloading - Consideration should be given to the connection of the equipment to the supply circuit and the
effect that overloading of the circuits might have on overcurrent protection and supply wiring. Appropriate
consideration of equipment nameplate ratings should be used when addressing this concern.
6. Reliable Earthing - Reliable earthing of rack-mounted equipment should be maintained. Particular attention should
be given to supply connections other than direct connections to the branch circuit (e.g. use of power strips).
7.
Only the screws provided with the mounting kit should used to attach the brackets to the control unit.
Installing IP500/IP500 V2
IP Office 9.0
for the individual IP Office units are still applicable inside the rack cabinet.
60
· Barrier Box Rack Mounting Kit (SAP 700293905)
environmental requirements
Barrier boxes must be used for
extensions
. This bracket allows up to 8 IP Office barrier boxes to
45
be rack mounted and simplifies the number of connections to the
protective ground point in the rack. This kit must be used when more
than 3 barrier boxes are in use and supports a maximum of 16
barrier boxes for a single external expansion module.
for an IP Office system, the following additional factors must be
60
IP500 V2 Installation: Wall Mounting
out-of-building analog phone
15-601042 Issue 28c (19 August 2013)
Page 89

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ip500

Table of Contents