Table A-1. Environmental Specifications, HP 3000 and HP 9000
Description
Operating Temperature
HP9000/Kx80 only 5° to 35° C (41° to 91° F)
Non-operating Temperature
Temperature Rate of Change
Over Temperature First Warning
Over Temperature Second Warning
with OS Shutdown
Over Temperature Hardware
Shutdown
Operating Humidity
Non-operating Humidity
HP 9000 Kx50/Kx60/Kx70/Kx80
and HP3000 979KS
Operating Altitude
Non-operating Altitude
Heat Dissipation (maximum load)
HP 9000 Kx50/Kx60/Kx70/Kx80
and HP3000 979KS
5° to 40° C (41° to 104° F)
-40° to 65° C (-40° to 149° F) (with no internal tape media device)
-40° to 45° C (-40° to 113° F) (with internal tape media device)
20° C (36° F)/hr. (with no internal tape media device)
10° C (18° F)/hr. (with internal tape media device)
35° C (95° F) Internal
40° C (104° F) Internal
43° C (109° F) Internal
15% to 80% RH non-condensing, max wet bulb
(at 26° C (79° F) with internal tape media device)
5% to 90% RH non-condensing (at 65° C/149° F) rate of change,
30% RH/hr.
5% to 80% RH non-condensing (at 65° C/149° F) rate of change,
30% RH/hr.
0 to 3.0 KM (0 to 10,000 ft) above sea level
0 to 4.5 KM (0 to 15,000 ft) above sea level
4263 BTU/hr.
5846 BTU/hr.