Christie Roadster S+ User Manual page 32

Christie dlp 3d projector user's manual
Table of Contents

Advertisement

INSTALLATION & SETUP
Separating Networks
2-26
Roadster/Mirage S+ User's Manual
session, but may change with subsequent power-ups and logins. On some networks,
the address will remain stable from session to session. In all cases, the projector's IP
address and port appear in the Status menu as well as the Ethernet Settings submenu.
See Figure 2.35
Figure 2.35. Setting the Projector's IP Address
Note that if a projector's IP address is anything other than 0.0.0.0 (shown as
000.000.000.000 in the Ethernet Settings menu) upon connection to an Ethernet
network, or if DHCP is not available on the network, the automatic DHCP server
function for supplying a valid and unique IP address to the projector is disabled.
Instead, a specific and static IP address must be defined in projector memory—enter
the new address in the Ethernet Settings submenu, or send to the projector via a serial
command.. The IP address will be in effect until it is changed again, or until the
DHCP checkbox is re-enabled for use with a DHCP server on the network.
NOTE: Only the port and IP address of the projector can be changed. The subnet
mask is fixed (255.255.255.0).
CHANGING THE PORT#:
require that the port number of the projector be changed from its default of 3002. If
so, enter a new port number in the Ethernet Settings menu or include the new port# in
an XIP serial command sent to the projector. It is highly recommended not to use a
port# below 1000, as these ports are typically reserved for and used by common IP
applications.
SUBNET MASK AND DEFAULT GATEWAY:
automatically assigned when DHCP is enabled. If a static IP is being used, it must be
assigned before the subnet mask. The Default Gateway is an optional router device
used to send and receive data outside the subnet.
ArtNet INTERFACE SETTINGS:
and Advanced Control, System Configuration – Communication for additional
information about ArtNet settings.
By default, communications originating from one type of serial controller—RS232
'
vs. RS422 vs. Ethernet—stay on the corresponding network path. A "Separate"
setting indicates this separation for "Network Routing" in the Communications menu.
If you are using an RS422 controller, for example, it will communicate only with the
projector to which it is connected unless you change this setting to either "RS232 and
RS422 Joined" or "All Joined" (Figure 2.36).
On some Ethernet networks, firewall restrictions may
The Subnet Mask and Default Gateway are
Refer to Section 3.6 – Adjusting System Parameters

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mirage s+

Table of Contents