Rpm10 Pressura Monitor; Bacnet ® Ms/Tp Object Set - Pressura RPM10 Operation And Service Manual

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

®
BACnet
MS/TP Object Set

RPM10 PresSura Monitor

Device
Object Type
Instance
Analog Input
1
Analog Input
2
Analog Input
3
Analog Input
6
Analog Input
10
Analog Value
1
Analog Value
2
Analog Value
3
Analog Value
4
Analog Value
5
Analog Value
11
Analog Value
39
Analog Value
40
Analog Value
41
Analog Value
42
Analog Value
43
Binary Input
1
Binary Input
4
Binary Value
1
Binary Value
2
Multi-State
3
Value
Multi-State
4
Value
88
*Units
Description
in H
O, Pa
Room1 Pressure
2
3
cfm, l/s, m
/hr
Supply Flow Rate
Air Changes Per
Hour
3
cfm, l/s, m
/hr
Exhaust Flow Rate
Room 1 Label
in H
O, Pa
Room 1 Neg Low
2
Alarm
in H
O, Pa
Room 1 Neg High
2
Alarm
in H
O, Pa
Room 1 Pos Low
2
Alarm
in H
O, Pa
Room 1 Pos High
2
Alarm
3
cfm, l/s, m
/hr
Room 1 Low
Exhaust Alarm
3
3
ft
, m
Room 1 Volume
Alarm Delay
Mute Timeout
Door Delay
Address
MAC ID
Room 1 Door Switch
Room 1 Occupancy
Room 1 High Alarm
Room 1 Low Alarm
Passcode Enable
Input 1
Configuration
Writable
Object
Value
Y
Y
Writing to Object name will
change Rm1 Label item.
Room 1 Label object has not
applicable in H
Updating Room 1 Label
Object name will not
affect other Room 1
Object names.
Y
-0.19500 to + 0.19500
in H
Y
-0.19500 to + 0.19500
in H
Y
-0.19500 to + 0.19500
in H
Y
-0.19500 to + 0.19500
in H
Y
0 to 30,000 cfm
Y
0 to 20,000
Y
20 to 600 seconds
Y
1 to 60 minutes
Y
20 to 600 seconds
Y
1 to 127
Y
0 to 999
Device ID =
1000*MAC ID + Address
0
1
0
1
0
1
0
1
Y
1
2
3
4
1
2
Notes and Range
O units.
2
O
2
O
2
O
2
O
2
Door Closed (Normal)
Door Open
Occupied (Normal)
Unoccupied
Disable
Enable
Disable
Enable
No Password
Room Mode Password
Menu Password
Menu & Room Mode
Passwords
TSI Sensor
Pressure Transducer
Appendix B