Pressura RPM10 Operation And Service Manual page 49

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

Input3 Config Menu
Sup Pres Flow
SOFTWARE
MENU ITEM
NAME
Set Flow Station
Sensor Zero
Zero Calibration
RPM10 and
RPM20
Set Maximum
Sensor Max
Sensor Pressure
Output
RPM10 and
RPM20
Set Minimum
Signal Min
Sensor Voltage
Output
RPM10 and
RPM20
Set Maximum
Signal Max
Sensor Voltage
Output
RPM10 and
RPM20
Flow Station Low
Low Cal
Calibration
RPM10 and
RPM20
Flow Station High
High Cal
Calibration
RPM10 and
RPM20
ITEM DESCRIPTION
The Sensor Zero item is used to re-zero the pressure
transducer zero calibration point.
The Sensor Max item is used to set the maximum reading
of a flow station and pressure transducer used to measure
supply air flow. For example, if the pressure transducer has
a range of 0 in H
O to +0.25 in H
2
Sensor Max should be set to +0.25 in H
The Signal Min item is used to set the minimum output
signal when a flow station and pressure transducer is used
to supply flow.
The Signal Max item is used to set the maximum output
signal when a flow station and pressure transducer is used
to measure supply flow.
The Low Cal menu item enters the Low Cal Submenu.
The High Cal menu item enters the High Cal Submenu.
O 0 to +62.5 Pa), the
2
O (+62.5 Pa).
2
See
See
DEFAULT
ITEM RANGE
VALUE
NONE
0 to 1.00 in H
O
1.00 in H
2
0 to 10 V
0 V
1 to 10 V
10 V
Flow Calibration
Flow Calibration
O
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rpm20

Table of Contents