Test - View Outputs
Enter the View Outputs item to view all output signals with real-time updates.
If the monitor passes each of the tests, the mechanical piece parts are all functioning correctly.

Troubleshooting Chart

Symptom
Possible Cause
Display is blank.
Fuse is blown.
DIM is defective.
Cannot access
menu
Need to display
--
model number
and firmware
revision
Measurements
Inputs not
in Diagnostics
configured.
mode read "Not
Configure"
Technical Section
Figure 17. View Outputs screen in Diagnostics menu
Corrective Action
Measure voltage at pins 1 and 2 on DIM 2-pin connector.
The voltage should nominally be 24 VAC.
If correct voltage is measured, internal DIM fuse is probably
blown. Unplug 2-pin connector from DIM for 2 minutes. The
internal fuse will automatically reset. Plug unit back in and
check display. If display is still blank, check all wiring, etc.
Verify circuit breaker is on.
Verify transformer primary measures 110 VAC.
Verify transformer secondary measures 24 to 30 VAC.
If proper voltage is found between pins 1 and 2 of the DIM,
all wiring has been checked, fuses have been reset, and
screen is still blank, the DIM is probably defective. Replace
DIM.
Slide finger across the screen diagonally from upper right to
lower left corner.
Enter the DIAGNOSTICS menu.
Enter the Configure menu to appropriately configure inputs.
67