Pressura RPM10 Operation And Service Manual page 58

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

Input5 Config Menu
RH
SOFTWARE
MENU ITEM
NAME
Set Minimum
Sensor Min
Sensor Output
RPM20
Set Maximum
Sensor Max
Sensor Output
RPM20
Set Minimum
Signal Min
Sensor Voltage
Output
RPM20
Set Maximum
Signal Max
Sensor Voltage
Output
RPM20
Adjust Sensor
Sensor Span
Calibration
RPM20
Reset Calibration
Reset Cal
RPM20
ITEM DESCRIPTION
The Sensor Min item is used to set the minimum reading
of the relative humidity sensor.
The Sensor Max item is used to set the maximum reading
of the relative humidity sensor.
The Signal Min item is used to set the minimum output
signal of the relative humidity sensor.
The Signal Max item is used to set the maximum output
signal of the relative humidity sensor.
The Sensor Span item is used to adjust the calibration of
the relative humidity sensor. The Sensor Span is an offset
adjustment and can only be adjusted by ±10% RH.
The Reset Cal item is used to return to the factory default
calibration, undoing any field calibration adjustments.
When this menu item is entered, the controller will prompt
the user to verify that they want to do this by displaying the
message "Reset Settings to Factory Default?" Entering
YES resets the Sensor Span factor for this sensor to
defaults. Entering NO will cancel the reset.
DEFAULT
ITEM RANGE
VALUE
0 to 100% RH
0% RH
0 to 100% RH
100% RH
0 to 10 V
0 V
1 to 10 V
10 V
-10% to +10% RH
0% RH
None
N/A