Pressura RPM10 Operation And Service Manual page 44

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

Input1 Config Menu
Press Trans
SOFTWARE
MENU ITEM
NAME
Set Minimum
Signal Min
Sensor Voltage
Output
RPM10 and
RPM20
Set Maximum
Signal Max
Sensor Voltage
Output
RPM10 and
RPM20
Set Sensor Zero
Sensor Zero
Calibration
RPM10 and
RPM20
Reset Calibration
Reset Cal
RPM10 and
RPM20
ITEM DESCRIPTION
The Signal Min item is used to set the minimum output
signal when a pressure transducer is used to measure
room pressure differential.
The Signal Max item is used to set the maximum output
signal when a pressure transducer is used to measure
room pressure differential.
The Sensor Zero item is used to re-zero the pressure
transducer zero calibration point.
The Reset Cal item is used to return to the factory default
calibration, undoing any field calibration adjustments.
When this menu item is entered, the monitor will prompt
the user to verify that they want to do this by displaying the
message "Are You Sure." Entering YES resets the Sensor
Zero factor for this sensor to defaults. Entering NO will
cancel the reset.
DEFAULT
ITEM RANGE
VALUE
0 to 5 V
0 V
1 to 10 V
10 V
None
N/A
None
N/A