Rm1 Alarm Menu
SOFTWARE
MENU ITEM
NAME
Room 1 Low
Exh Low Alm
Exhaust Flow
Alarm
RPM10 and
RPM20
Room 1 Low
Sup Low Alm
Supply Flow Alarm
RPM10 and
RPM20
Room 1 Low Room
Temp Low
Temperature Alarm
Alm
RPM20
High Room
Temp Hi Alm
Temperature Alarm
RPM20
Low Relative
RH Low Alm
Humidity Alarm
RPM20
High Relative
RH Hi Alm
Humidity Alarm
RPM20
ITEM DESCRIPTION
The Exh Low Alm item sets the minimum exhaust flow
alarm setpoint. A minimum flow alarm is defined as when
the exhaust flow is less than the Exh Low Alm setpoint.
The Sup Low Alm item sets the minimum supply flow
alarm setpoint. A minimum flow alarm is defined as when
the supply flow is less than the Sup Low Alm setpoint.
The Temp Low Alm item sets the minimum room
temperature alarm setpoint.
The Temp Hi Alm item sets the maximum room
temperature alarm setpoint.
The RH Low Alm item sets the minimum relative humidity
alarm setpoint.
The RH Hi Alm item sets the maximum relative humidity
alarm setpoint.
ITEM RANGE
DEFAULT VALUE
0 to 30,000 cfm
0 to 30,000 cfm
50 to 100°F
Note: Temp Low Alm
cannot be set
greater than the
Temp Hi Alm
50 to 100°F
Note: Temp Hi Alm
cannot be set
less than the
Temp Low Alm
0 to 100%
Note: RH Low Alm
cannot be set
greater than the
RH Hi Alm
0 to 100%
Note: RH Hi Alm
cannot be set
less than the
RH Low Alm
0 cfm
0 cfm
50°F
100°F
0%
100%