Example Of 03 Read Holding Registers Function Format - Pressura RPM10 Operation And Service Manual

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

EXAMPLE of 03 Read Holding Registers function format:

This example reads the face velocity and current face velocity set point.
QUERY
Field Name
(Hex)
Slave Address
01
Function
03
Starting Address Hi
00
Starting Address Lo
00
No. Of Registers Hi
00
No. Of Registers Lo
02
Error Check (CRC)
--
82
RESPONSE
Field Name
Slave Address
Function
Byte Count
Data Hi
Data Lo
Data Hi
Data Lo
Error Check (CRC)
(Hex)
01
03
04
00
64 (100 ft/min)
00
64 (100 ft/min)
Appendix B

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rpm20

Table of Contents