Pressura RPM10 Operation And Service Manual page 39

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

Interface Menu
SOFTWARE
MENU ITEM
NAME
Analog Output
AO1 Sig
Signal Type
Type
RPM10 and
RPM20
Analog Output
AO2 Sig
Signal Type
Type
RPM10 and
RPM20
Analog Output
AO2 Out
Signal
Type
RPM10 and
RPM20
Analog Output Full
AO2 Sig
Scale
Rnge
RPM10 and
RPM20
ITEM DESCRIPTION
The AO1 Sig Type item selects the measurement that the
analog output signal will represent.
The AO2 Sig Type item selects the measurement that the
analog output signal will represent.
The AO2 Out Type item selects the analog output (not
control output signal).
The AO2 Sig Rnge item selects the full scale range that
the analog output signal will represent. If the room pressure
sensor is set to:
AO2 SIGNAL TYPE
(SENSOR)
0 V / 4 mA
ROOM 1
- AO2 Sig Rnge
PRESSURE (TSI)
ROOM 1
PRESSURE
(PRESSURE
TRANSDUCER;
SENSOR MIN=0)
ROOM 1
- AO2 Sig Rnge
PRESSURE
(PRESSURE
TRANSDUCER;
SENSOR MIN≠0)
EXHAUST FLOW
NOTE: Do not set AO2 Sig Rnge to a value greater than
the sensor input.
10 V / 20 mA
+ AO2 Sig Rnge
0
AO2 Sig Rnge
+ AO2 Sig Rnge
0
AO2 Sig Rnge
DEFAULT
ITEM RANGE
VALUE
None
None
Room 1 Pressure
None
Exhaust Flow
None
0 to 10 VDC
0 to 10 VDC
4-20 mA
PRESSURE:
PRESSURE:
-1.00 in H
O
0.10 in H
2
to
+1.00 in H
O
FLOW:
2
1000 CFM
FLOW: 0 to
30,000 CFM
O
2