Interface Menu
SOFTWARE
MENU ITEM
NAME
Analog Output
AO3 Sig
Signal Type
Type
RPM20
Analog Output
AO3 Out
Signal
Type
RPM20
Analog Output Full
AO3 Sig
Scale
Rnge
RPM20
ITEM DESCRIPTION
The AO3 Sig Type item selects the measurement that the
analog output signal will represent.
The AO3 Out Type item selects the analog output (not
control output signal).
The AO3 Sig Rnge item selects the full scale range that
the analog output signal will represent. If the room pressure
sensor is set to:
AO3 SIGNAL
TYPE (SENSOR)
0 V / 4 mA
ROOM 2
-AO3 Sig Rnge
PRESSURE
(TSI)
ROOM 1
0
PRESSURE
(PRESSURE
TRANSDUCER;
SENSOR MIN=0)
ROOM 1
-AO3 Sig Rnge
PRESSURE
(PRESSURE
TRANSDUCER;
SENSOR MIN≠0)
SUPPLY FLOW
0
EXHAUST
0
FLOW
NOTE: Do not set AO3 Sig Rnge to a value greater than
the sensor input.
ITEM RANGE
Room 2 Pressure
Supply Flow
Exhaust Flow
None
0 to 10 VDC or
4-20 mA
PRESSURE:
-1.00 in H
to
+1.00 in H
FLOW: 0 to
10 V / 20 mA
30,000 CFM
+ AO3 Sig Rnge
AO3 Sig Rnge
+ AO3 Sig Rnge
AO3 Sig Rnge
AO3 Sig Rnge
DEFAULT
VALUE
None
0 to 10 VDC
PRESSURE:
O
0.10 in H
O
2
2
FLOW:
O
1000 CFM
2