Pressura RPM10 Operation And Service Manual page 86

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

RPM20 Variable List
Variable Name
Relay 2
6
Configuration
Input 1
7
Configuration
Input 2
8
Configuration
Input 3
9
Configuration
Input 4
10
Configuration
Input 5
11
Configuration
Input 6
12
Configuration
Input 7
13
Configuration
Room 1 Mode
14
Room 1 Low Alarm
15
Enable
Room 1 High Alarm
16
Enable
Room 1 Negative
17
Low Alarm Setpoint
Room 1 Negative
18
High Alarm Setpoint
Room 1 Positive
19
Low Alarm Setpoint
78
Variable
Address
Read/Write
Read
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Integer DDC system receives
1
High Alarm
2
Negative Room Mode
3
Positive Room Mode
1
TSI Sensor
2
Pressure Transducer
1
TSI Sensor
2
Pressure Transducer
4
None
1
Supply Pressure Flow
2
Supply Linear Flow
3
Supply Venturi
4
Supply Switch
5
TSI Sensor
6
Pressure Transducer
7
None
1
Room 1 Door Switch
2
Room 1 Occupancy Sensor
3
None
1
Room 1 Key Switch
2
Relative Humidity
3
None
1
Room 1 Temperature
3
Room 2 Occupancy Sensor
4
Room 2 Door Switch
6
None
2
Exhaust Pressure Flow
3
Exhaust Linear Flow
4
Exhaust Venturi
5
Exhaust Switch
6
Room 2 Key Switch
8
None
1
Positive
2
Negative
3
No Isolation
1
Disabled
2
Enabled
1
Disabled
2
Enabled
Displayed in inches H
O.
2
Host DDC system must divide value by
100,000 to report pressure correctly
Displayed in inches H
O.
2
Host DDC system must divide value by
100,000 to report pressure correctly
Displayed in inches H
O.
2
Host DDC system must divide value by
100,000 to report pressure correctly
Appendix B