Rm1 Temp; Rm2 Occ Sen; Rm2 Dr Sw - Pressura RPM10 Operation And Service Manual

Room pressure monitor
Hide thumbs Also See for RPM10:
Table of Contents

Advertisement

Input6 Config Menu

Rm1 Temp

SOFTWARE
MENU ITEM
NAME
Adjust Sensor
Sensor Span
Calibration
RPM20
Reset Calibration
Reset Cal
RPM20
Input6 Config Menu

Rm2 Occ Sen

SOFTWARE
MENU ITEM
NAME
Signal to Indicate
Unocc Sig
Room Unoccupied
RPM20
Input6 Config Menu

Rm2 Dr Sw

SOFTWARE
MENU ITEM
NAME
Signal to Indicate
Dr Open Sig
Open Door
RPM20
ITEM DESCRIPTION
The Sensor Span item is used to adjust the calibration of
the temperature sensor.
The Reset Cal item is used to return to the factory default
calibration, undoing any field calibration adjustments.
When this menu item is entered, the controller will prompt
the user to verify that they want to do this by displaying the
message "Reset Settings to Factory Default?" Entering
YES resets the Sensor Span factor for this sensor to
defaults. Entering NO will cancel the reset.
ITEM DESCRIPTION
The Unocc Sig item is used to set the signal that indicates
the room is unoccupied.
ITEM DESCRIPTION
The Dr Open Sig item sets the signal the Model RPM20
Room Pressure Monitor will receive to indicate a door is
open.
DEFAULT
ITEM RANGE
VALUE
-10F to +10°F
0°F
None
N/A
DEFAULT
ITEM RANGE
VALUE
Open, Closed
Closed
DEFAULT
ITEM RANGE
VALUE
Open, Closed
Closed